Megger LRCD220 Combined Loop and RCD Tester — Field Installation Checks

205 views
Delivery
  • Megger LRCD220 combined loop and RCD tester for UAE electrical contractors. Adds 1000 mA RCD testing, wider supply range and phase-rotation checks versus lower LRCD models. IP54 case, about 980 g. Inquire for Dubai stock.

Repair request

Megger LRCD220 Combined Loop and RCD Tester — Field Installation Checks · Megger

Step 1 — Instrument details

Step 2 — Contact & return address

Return shipping address

Step 3 — Comments & confirm


Serial number:
What is wrong:
· ·

Request a Rental Quote

Megger LRCD220 Combined Loop and RCD Tester — Field Installation Checks

Step 1 — Rental Details

Step 2 — Contact Information

Step 3 — Confirm

Megger LRCD220 Combined Loop and RCD Tester — Field Installation Checks
Quantity:  ·  Term:
Start date: –
·

Certificate request

Megger LRCD220 Combined Loop and RCD Tester — Field Installation Checks · Megger

Step 1 — Device

First tell us if you already have this product, or want the certificate included with a purchase.

Step 2 — Certificates

Select one or more certificates. Prices shown are optional list prices when the admin set them; otherwise we quote after review.

Step 3 — Your details

Contact

Shipping / return address

Selected Documents Action
Added to compare list
Order above 1000 AED = Free Delivery
Delivery by * within UAE. When you order in
This item will be delivered by .
Want it Tomorrow?
Select Click & Collect on checkout within the next
Secure Transaction
This item is eligible for return (for Warranty only)
Online support
24/7 Support
Original Products
quality guarantee
Fast Delivery
Fastest delivery ever!
Online payment
fast and safe
secure and live track
fast and safe
Description

About this model

The Megger LRCD220 is a combined loop-impedance and residual-current-device tester for installation verification. It consolidates loop and RCD checks in one handheld unit so electricians spend less time swapping instruments on site. Uazon lists it under RCD Tester, SKU MEGGER-RCDTESTE-LRCD220.

MM Electronics / Uazon supplies Megger in the UAE on a non-exclusive basis through 31 December 2026.

Megger LRCD220 loop and RCD tester for installation compliance

Key capabilities include:

  • Full RCD coverage including standard, DC-sensitive and selective devices, with a 1000 mA range on the LRCD220.
  • Automatic RCD sequences that cut repetitive manual steps on multi-point jobs.
  • Ramp testing to find the trip threshold instead of only pass/fail.
  • High-current and non-trip loop paths, plus phase-rotation indication for three-phase work.
  • IP54 rubber-armoured case and a backlit display for dim panels and outdoor sites.

Compared with LRCD200/210 rows in the same table, the LRCD220 widens supply to 100–280 V and adds the 1000 mA RCD step.

Megger LRCD220 next to other Uazon loop/RCD options

Match the instrument to the job:

  • LRCD210 is the related lower model on Uazon. Compare with the LRCD210 product page to see the differences versus the 220.
  • This LRCD220 is the storage/download-focused instrument.

Same-site paths for the buyer:

Megger LRCD220 questions for contractors

What does the LRCD220 add over LRCD210?

The side-by-side table shows: 1000 mA RCD step, 100–280 V RCD/loop supply window (vs 200–280 V on 200/210), and the broader commercial feature set described on the page (auto sequences, ramp, phase rotation, backlight).

Is it 3-phase safe?

The product information states the device is designed to be 3-phase safe and includes phase-rotation verification.

How heavy is it?

980 g; 203 × 148 × 78 mm; IP54.

Is a Dubai price listed?

No. Inquire with Uazon.

Inquire for Dubai stock. Call +971 4 447 6031 or +971 4 344 9868, or email info@uazon.ae. Desk: No 403, 4th Floor, Deira Creek, Radisson Blu Hotel, Plaza Bldg, Dubai, UAE. Confirm availability — Discontinued and In stock badges both show.

Specification
SPECIFICATIONS – LRCD200 / LRCD210 / LRCD220
Voltage Measurement (LRCD200, 210, 220)
Range 0 V - 500 V
Accuracy ±2% ±2 digits
Frequency Measurement (LRCD200, 210, 220)
Range 25 Hz - 450 Hz
Accuracy 25.0 - 199.9 Hz: ±0.1 Hz
200 - 450 Hz: ±1 Hz
Phase Rotation Indicator (LRCD220 only)
Description Three-wire identification of phase rotation
Frequency 45 Hz - 65 Hz
Loop Testing (to EN 61557-3)
No Trip Loop Test (3-wire, Line to Earth)
Supply LRCD200/210: 200 V - 280 V, 45 - 65 Hz
LRCD220: 100 V - 280 V, 45 - 65 Hz
Nominal Test Current 15 mA
Loop Accuracy 0.01 - 9.99 Ω: ±5% ±0.03 Ω
10.0 - 99.9 Ω: ±5% ±0.5 Ω
100 - 999 Ω: ±5% ±5 Ω
1.00 - 2.00 kΩ: ±5% ±30 Ω
High Current Line/Earth Loop Test (2-wire, LRCD220 only)
Supply 100 V - 480 V
Nominal Test Current 15 mA - 2.4 A
Loop Accuracy 0.01 - 9.99 Ω: ±5% ±0.03 Ω
10.0 - 99.9 Ω: ±5% ±0.5 Ω
100 - 999 Ω: ±5% ±5 Ω
1.00 - 2.00 kΩ: ±5% ±30 Ω
Line/Line (LRCD220 only)
Supply 100 V - 480 V, 45 - 65 Hz
Prospective Fault Current (PSCC)
Description Prospective fault current = Nominal supply voltage / Loop resistance
Accuracy derived from loop test
Resolution 1 - 199 A: 1 A resolution
0.20 - 1.99 kA: 10 A resolution
2.0 - 19.9 kA: 100 A resolution
RCD Testing (to EN61557-6)
RCD Test Ranges LRCD200/210: 10 mA, 30 mA, 100 mA, 300 mA, 500 mA
LRCD220: 10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 1000 mA
Supply Voltage LRCD200/210: 200 - 280 V, 45 - 65 Hz
LRCD220: 100 - 280 V, 45 - 65 Hz
Test Current Accuracy No Trip Test (½I): −8% to −2%
Trip Test (I, 5I): +2% to +8%
Trip Time ±1% ±1 ms
Fault (Touch) Voltage
Displayed Range 0 - 50 V
Error +5% / +15% ±0.5 V
Temperature and Humidity
Operating Range −5°C to +40°C
Operating Humidity 93% RH at +40°C max
Storage Range −25°C to +70°C
Maximum Altitude 2000 m
Environmental Protection IP54
Safety
Standard IEC 61010
Category Meets IEC61010-1 Cat III 300 V phase to earth
EN61557 Compliance Part 1 – General Requirements
Part 3 – Loop Resistance
Part 6 – Residual Current Devices
Power Supply
Battery 8 × 1.5 V IEC LR6 type (AA alkaline)
Rechargeable 8 × 1.2 V NiCd or NiMH cells
Battery Life 2000 consecutive tests
Physical
Weight 980 g
Dimensions 203 × 148 × 78 mm
E.M.C.
Standard In accordance with IEC61326-1
Downloads
FAQs & How To

FAQs

The Megger LRCD220 Combined Loop and RCD Testers are professional instruments used to verify loop impedance and RCD operation in electrical systems.
Contact us through the store; we reply within one business day.
You can buy them from uazon.ae through an authorized distribiutor operating with a retail hybrid model.
It is used for loop impedance testing and RCD performance checks during installation, maintenance, and commissioning.

How To

Steps for performing loop and RCD tests using the Megger LRCD220.

Estimated Time: PT12M

Check that the Megger LRCD220 is in proper working condition and ready for testing.
Attach the leads securely to the outlet or circuit under test.
Select loop mode and start the test to obtain impedance readings.
Switch to RCD mode and trigger the device to evaluate trip performance.
Record the measured results for compliance, reporting, or safety evaluation.