final confirmation from support is required. Once your order is placed, please await final confirmation from the company. (+97144476031)
Fluke 1664 FC Splendid Installation Multifunction Tester
0.00 AED
In stock
Product Details
UPC:
095969850148
Brand:
Fluke
AC voltage Range:
500 V
AC voltage Resolution:
0.1 V
Continuity Range:
20 Ω / 200 Ω / 2000 Ω
Continuity Resolution:
0.01 Ω / 0.1 Ω / 1 Ω
Insulation resistance Test voltage:
50-100-250-500-1000 V
Insulation resistance range:
20 MΩ / 50 MΩ / 100 MΩ / 200 MΩ / 500 MΩ / 1000 MΩ
Loop and line impedance:
10 Ω (Hi current mΩ mode)/20 Ω/200 Ω/2000 Ω
Earth Resistance Range:
200 Ω / 2000 Ω
Dimentions:
10 x 25 x 12.5 cm
Weight :
1.3 Kg
Power:
Type AA, 6 ea.
IP rating:
IP40
Overvoltage:
CAT III / 500V; CAT IV 300V
Fluke 1664 FC Splendid Installation Multifunction Tester
The Fluke 1664 FC Splendid Installation Multifunction Tester is a versatile and reliable tool designed for professional installers and troubleshooters working in various electrical applications. It offers a wide range of measurement functions, built-in memory storage, and easy-to-configure testing procedures, making it an ideal choice for hardworking professionals.
Fluke 1664 FC Key Features
- Insulation PreTest: The device can perform an Insulation PreTest, which stops the insulation test and helps avoid potentially serious and costly mistakes that can cause damage to customers' installations.
- Auto Test: The Fluke 1664 FC can perform up to seven installation tests in one sequence, ensuring compliance with local installation regulations. This reduces the number of manual connections, thus decreasing the possibility of errors and reducing test time.
- Continuity Testing: The tester can test continuity at L-N, N-PE inputs, and L-PE inputs.
- Smooth DC Sensitive RCD Testing: The fluke 1664fc multifunction tester can test smooth DC sensitive RCDs (Type B) for Type B/B+ RCDs.
- Earth Resistance, Voltage, and Frequency Measurements: The device can measure earth resistance, voltage, and frequency.
Fluke Multifunction Tester 1664
The Fluke 1664 FC Installation Multifunction Tester is compact and lightweight, weighing less than 1.3 kg, and comes with a padded carrying and waist strap for convenient handling. It is designed for use in harsh environments and meets safety standards IEC 61010-1 600 V CAT III, double or reinforced insulation, pollution degree 2, and protection standards IP40. The device is suitable for various applications, including load studies, energy assessments, harmonics measurements, and voltage event capture. It is commonly used in petrochemical, oil and gas, pharmaceutical, water and wastewater, food and beverage, and power generation industries.
In summary, the Fluke 1664 FC Installation Multifunction Tester is a feature-rich and reliable instrument that offers high accuracy, ease of use, and versatility, making it suitable for a wide range of applications in different industries. Its comprehensive functionality, large memory capacity, and rugged design make it an ideal tool for power quality logging, energy studies, and load studies. The device is a valuable tool for professionals who require precise and reliable power quality logging and energy studies in their day-to-day work.
Fluke 1664 FC Specifications
AC voltage measurement | ||||
Range | 500 V | |||
Resolution | 0.1 V | |||
Accuracy 45 Hz – 66 Hz | 0.8% + 3 | |||
Input impedance | 360 kΩ | |||
Overload protection | 660 V rms | |||
Continuity testing (RLO) | ||||
Range (autoranging) | 20 Ω / 200 Ω / 2000 Ω | |||
Resolution | 0.01 Ω / 0.1 Ω / 1 Ω | |||
Open Circuit Voltage | >4 V | |||
Insulation resistance measurement (RISO) | ||||
Test voltages | 50-100-250-500-1000 V | |||
Accuracy of test voltage (at rated test current) | +10%, -0% | |||
Test voltage | 50 V | |||
100 V | ||||
250 V | ||||
500 V | ||||
1000 V | ||||
Insulation resistance range | 20 MΩ / 50 MΩ | |||
20 MΩ / 100 MΩ | ||||
20 MΩ / 200 MΩ | ||||
20 MΩ / 200 MΩ / 500 MΩ | ||||
20 MΩ / 200 MΩ / 1000 MΩ | ||||
Resolution | 0.01 MΩ / 0.1 MΩ | |||
0.01 MΩ / 0.1 MΩ | ||||
0.01 MΩ / 0.1 MΩ | ||||
0.01 MΩ / 0.1 MΩ / 1 MΩ | ||||
0.01 MΩ / 0.1 MΩ / 1 MΩ | ||||
Test current | 1 mA @ 50 kΩ | |||
1 mA @ 100 kΩ | ||||
1 mA @ 250 kΩ | ||||
1 mA @ 500 kΩ | ||||
1 mA @ 1 MΩ | ||||
Loop and line impedance (ZI) | ||||
Range | 10 Ω (Hi current mΩ mode)/20 Ω/200 Ω/2000 Ω | |||
Resolution | 0.001 Ω/ 0.01 Ω/ 0.1 Ω/1 Ω | |||
Prospective earth fault current, PSC test | ||||
Range | 1000 A / 10 kA (50 kA) | |||
Resolution | 1 A / 0.1 kA | |||
Computation | Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively. | |||
RCD testing, RCD types tested | ||||
RCD Type | AC¹ | |||
G²,S³ | ||||
Model 1663 | A4, AC¹, G²,S³ | |||
Model 1664 FC | A, AC, B5, S | |||
Notes | ¹Responds to AC | |||
²General, no delay | ||||
³Time delay | ||||
⁴Responds to pulsed signal | ||||
⁵Responds to smooth DC signal | ||||
Tripping speed test (ΔT) | ||||
Current settings¹ | 10-30-100-300-500-1000 mA – VAR | |||
10-30-100 mA | ||||
Multiplier | x ½, x 1 | |||
x 5 | ||||
VAR Mode Type B - 6, 60, 200 mA | ||||
Measurement range | RCD Type G | 310 ms | ||
50 ms | ||||
RCD Type S | 510 ms | |||
160 ms | ||||
EV / RDC-DD | 6 mA - 10s | |||
60 mA - 0.3s | ||||
200 mA - 0.1s | ||||
Notes | ¹1000 mA type AC only | |||
700 mA maximum type A in VAR mode | ||||
The VAR Mode at RCD type B (smooth DC currents) generates the test currents acc. to IEC 62955 for RCD type A-EV or RDC-DD (6/60/200 mA and ramp <2 to 6 mA). | ||||
RCD/FI-Tripping Current Measurement/Ramp Test (IΔN) | ||||
Current range | 30% to 110% of RCD rated current¹ | |||
<2 mA to 6 mA smooth DC³ | ||||
Step size | 10% of IΔN² | |||
Linear rising within 30 s | ||||
Dwell time | RCD Type G | 300 ms/step | ||
RCD Type S | 500 ms/step | |||
Measurement accuracy | ±5% | |||
Specified trip current ranges (EN 61008-1) | 50% to 100% for Type AC | |||
35% to 140% for Type A (>10 mA) | ||||
35% to 200% for Type A (≤10 mA) | ||||
50% to 200% for Type B | ||||
Notes | ¹30% to 150% for Type A IΔN > 10 mA | |||
30% to 210% for Type A IΔN = 10 mA | ||||
20% to 210% for Type B | ||||
²5% for Type B | ||||
³For RCD type A-EV/RDC-DD acc. to IEC 62955 | ||||
Earth Resistance Test (RE) | ||||
Range | 200 Ω / 2000 Ω | |||
Resolution | 0.1 Ω / 1Ω | |||
Frequency | 128 Hz | |||
Output Voltage | 25 V | |||
Phase Sequence Indication | ||||
Icon |
|
|||
General Specifications | ||||
Size (L x W x H) | 10 x 25 x 12.5 cm | |||
Weight (incl. batteries) | 1.3 Kg | |||
Battery size, quantity | Type AA, 6 ea. | |||
Sealing | IP-40 | |||
Safety | Complies with EN/IEC 61010-1 and EN/IEC 61010-2-034 | |||
Overvoltage | CAT III / 500V; CAT IV 300V | |||
Performance | EN61557-1 to EN61557-7 and EN61557-10 |