final confirmation from support is required. Once your order is placed, please await final confirmation from the company. (+97144476031)
Fluke 1507 Insulation Resistance Tester
0.00 AED
In stock
Product Details
UPC:
095969288675
Brand:
Fluke
Insulation Range:
0.01 MΩ to 10 GΩ
Test Voltage Range:
50 V, 100 V, 250 V, 500 V, 1000 V
DC voltage Range:
600.0 V
AC voltage Range:
600.0 V
Fluke 1507 Insulation Tester
The Fluke 1507 is a portable, versatile and compact insulation tester
for advanced industrial and insulation testing. Its wide range of test voltages makes it ideal for a wide range of troubleshooting, commissioning and preventive maintenance applications.
Take advantage of the 1507's full feature set to perform advanced insulation resistance testing quickly and easily. Convenient size and light weight make it easy to pack and use. Additional features, like remote probes, save time and money, especially during repetitive testing.And the reasonable price and reliability certainly make it great value for money. for fluke 1507 insulation tester price visit uazon website.
Fluke Megger 1507 Features
- Rugged, compact advanced insulation resistance tester for electrical contractors and industrial and commercial electricians
- Automatically calculates Polarization Index and Dielectric Absorption Ratio
- Makes repetitive tests simple and easy with a Compare (Pass/Fail) function
- Offers multiple insulation test voltages: 50 V, 100 V, 250 V, 500 V, and 1000 V
Fluke 1507 Specification
AC/DC Voltage Measurement | ||
Accuracy | Range | 600.0 V |
Resolution | 0.1 V | |
50 Hz to 400 Hz ± (% of Rdg + Digits) | ±(2% + 3) | |
Input impedance | 3 MΩ (nominal), < 100 pF | |
Common mode rejection ratio (1 kΩ unbalanced): | > 60 dB at DC, 50 or 60 Hz | |
Overload protection | 600 V rms or DC | |
Earth Bond Resistance Measurement | ||
Range/Resolution | 20.00 Ω | 0.01 Ω |
200.0 Ω | 0.1 Ω | |
2000 Ω | 1.0 Ω | |
20.00 kΩ | 0.01 kΩ | |
Accuracy | ±(1.5% + 3) | |
Overload protection | 2 V rms or DC | |
Open circuit test voltage | > 4.0 V, < 8 V | |
Short circuit current | > 200.0 mA | |
Insulation Specifications | ||
Measurement range | 0.01 MΩ to 10 GΩ | |
Test voltage | 50 V, 100 V, 250 V, 500 V, 1000 V | |
Test voltage accuracy | + 20%, - 0% | |
Short circuit current | 1 mA nominal | |
Auto discharge | Discharge time < 0.5 second for C = 1 µF or less | |
Live circuit indicator | Inhibit test if terminal voltage > 30 V prior to initialization of test | |
Maximum capacitive load | Operable with up to 1 µF load | |
Measure accuracy | 50 V | ±(3% + 5) |
100 V | ±(3% + 5) | |
250 V | ±(1.5% + 5) | |
500 V | ±(1.5% + 5) | |
1000 V | ±(1.5% + 5) to 2000 MΩ, ±(10% + 3) above 2000 MΩ | |
General Specifications | ||
Maximum voltage applied to any terminal: | 600 V AC rms or DC | |
Storage temperature | -40°C to 60°C (-40°F to 140°F) | |
Operating temperature | -20°C to 55°C (-4°F to 131°F) | |
Temperature coefficient | 0.05 x (specified accuracy) per °C for temperatures < 18°C or > 28°C (< 64°F or > 82°F) | |
Relative humidity | ||
0% to 95% @ 10°C to 30°C (50°F to 86°F) | ||
0% to 75% @ 30°C to 40°C (86°F to 104°F) | ||
0% to 40% @ 40°C to 55°C (104°F to 131°F) | ||
Vibration | Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument | |
Shock | 1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor) | |
Electromagnetic compatibility | In an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997) | |
Safety | Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V (CAT IV) | |
Certifications | CSA per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN 61010-1 2nd Edition | |
Batteries | Four AA batteries (NEDA 15A or IEC LR6) | |
Battery life | Insulation test use: | Tester can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. |
Resistance measurements: | Tester can perform at least 2500 earth bond resistance measurements with fresh alkaline batteries at room temperature. These are standard tests of 1 Ω with a duty cycle of 5 seconds on and 25 seconds off. | |
Size (H x W x L) | 5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in) | |
Weight | 550 g (1.2 lb) | |
IP rating | IP40 | |
Altitude | Operating | 2000 m CAT IV 600 V, 3000 m CAT III 600 V |
Non-operating (storage) | 12,000 m | |
Over-range capability | 110% of range | |
Included accessories | TL224 Test Leads, TP74 Test Probes, clips PN 1958654 (red) and PN 1958646 (black), holster and remote probe |