  • Input Voltage Range: 380 V to 575 V (±5%) across single-phase models
  • Input Current Options: 200 A and 350 A
  • Input Frequency: 50 Hz and 60 Hz availability
  • Designed for industrial power applications
Order above 500 AED = Free Delivery
Delivery by * within UAE. When you order in
This item will be delivered by .
Want it Tomorrow?
Select Click & Collect on checkout within the next
We are not Supporting COD Payments Terms Outside UAE
Secure Transaction
This item is eligible for return
Online support
24/7 Support
Original Products
quality guarantee
Fast Delivery
Fastest delivery ever!
Online payment
fast and safe
secure and live track
fast and safe
Description

About this model

Megger DDA-3000 and DDA-6000 Universal Circuit Breaker Test Sets

The Megger DDA-3000 and DDA-6000 are designed specifically to test low-voltage power and molded-case circuit breakers equipped with thermal, magnetic, or solid-state trip devices. These advanced test sets utilize a unique transformer and circuit design, resulting in a very high-capacity test solution packed into a remarkably compact size. Advanced digital control and instrumentation provide exact testing capacity, ensuring reliable and precise results in the field. When considering the Megger DDA-3000 Price or looking to Buy Megger DDA-6000, it is essential to understand how these units solve critical testing challenges for electrical professionals.

Technical Features and Field Applications of the Megger DDA-3000 and DDA-6000

The versatility of the DDA series extends beyond simple breaker testing. These test sets can also be utilized for other high-current applications, such as verifying the ratio of current transformers and performing heat runs or primary injection testing of high-voltage breakers and their associated protective relays. For procurement teams seeking the Best Price Megger DDA-3000, the value lies in its multi-functional capability, which consolidates multiple testing requirements into a single, portable device. This comprehensive approach to testing ensures that field technicians have the tools necessary to maintain electrical safety and compliance efficiently.

Input Power Flexibility and Global Compatibility

Because Model DDA-3000 and DDA-6000 are used all over the world to test low-voltage circuit breakers, the design accounts for significant variations in power infrastructure. When ordering, select the test set that best suits the power system available at your facility. When you Buy Megger DDA-6000, you are investing in a platform engineered to contend with many different input voltages and frequencies, ensuring global operational flexibility. This adaptability makes the DDA series a preferred choice for multinational corporations and testing laboratories that require consistent performance across diverse geographic locations.

Optimized Output Performance and Impedance Management

The output circuit of the DDA series is engineered for maximum adaptability. The output of the test set is easily adjustable from zero to the maximum current available through the impedance of the device under test. Two output ranges are provided to accommodate a variety of load circuit impedances, allowing technicians to tailor the test parameters precisely. For high-impedance devices, the output can be connected in series using the series bar provided to double the output voltage at a reduced maximum current. Understanding these specifications is vital when evaluating the Megger DDA-6000 Price, as the ability to handle high-impedance loads efficiently translates to broader testing capabilities in the field.

The maximum current available from the test set is determined primarily by the impedance of the load circuit, while the duration of the available current is determined primarily by thermal conditions within the test set. This thermal management design ensures safety and longevity, preventing overheating during demanding testing cycles. The DDA-3000 and DDA-6000 are built to sustain rigorous use, providing reliable data for critical maintenance decisions.

Advanced Output Connections and Accessory Integration

To provide maximum utilization of the output available from the test set, each unit is equipped with a Megger stab adapter board and stab sets Model CBS-1 and Model CBS-2 for use with draw-out style and metal-clad breakers. These stabs eliminate the significant losses that occur if leads are used to connect the breaker under test to the test set. When you Buy Megger DDA-3000, you receive these specialized accessories that ensure efficient energy transfer and accurate test results. For applications involving molded-case breakers or other devices that will not connect directly to the stabs, cables must be used to establish a secure connection.

Duty Cycle and Operational Endurance

Reliability in the field depends on the ability of the equipment to perform under continuous load. The DDA series will supply the rated continuous current indicated for 30 minutes, followed by 30 minutes off. This duty cycle is designed to balance high-output performance with thermal recovery, ensuring the test set remains operational throughout a full day of testing. When comparing the Best Price Megger DDA-6000, the robust duty cycle specification is a critical factor that supports uninterrupted testing workflows, reducing downtime and increasing technician productivity.

Specification
Model No. Input Voltage (Single-Phase) Input Frequency Input Current
DDA-3000 460 V ±5% 60 Hz 200 A
DDA-3001 380 V ±5% 50 Hz 200 A
DDA-3002 415 V ±5% 50 Hz 200 A
DDA-6000 460 V ±5% 60 Hz 350 A
DDA-6001 380 V ±5% 50 Hz 350 A
DDA-6002 415 V ±5% 50 Hz 350 A
DDA-6004 575 V ±5% 60 Hz 350 A