The Megger Torkel 950 Battery Load Unit is a cutting-edge solution for conducting load/discharge testing on battery systems. It forms part of the Torkel 900 series, known for its high-performance capabilities and flexibility in testing various types of batteries.
The Torkel 950 is designed to perform load/discharge testing, allowing users to accurately determine the actual capacity of battery systems. It offers multiple testing modes, including constant current, constant power, constant resistance, and user-defined load profiles, providing a comprehensive assessment of battery performance.
You can compare the Megger Torkel 950 price with other suppliers in UAE and choose the best one.
Category | Specification |
Temperature | |
Operating | 0°C to +50°C (32°F to +122°F). Power derating at temperatures over +35°C (+95°F). |
Storage & Transport | -40°C to +70°C (-40°F to +158°F) |
Humidity | 5% – 95% RH, non-condensing |
Shock/Vibration/Fall | |
Instrument Only | ETSI EN 300 019-2-7 class 7M2 |
Instrument in Transport Case | ISTA 2A |
Altitude | |
Operating | 3000 m (10000 ft) |
Storage | 10000 m (33000 ft) |
Encapsulation Class | IP20 |
CE-Marking | |
LVD | IEC61010-1:2010 & IEC61010-2-030 |
EMC | IEC61326-1 |
General | |
Mains Voltage | 100 – 240 V AC, 50/60 Hz |
Power Consumption | 200 W (max) |
Power Interruption | 40 ms (max) |
Protection | Thermal cut-outs, Automatic overload protection, Emergency stop button |
Dimensions | 519x315x375 mm, (20.5”x12.4”x14.7”) |
Weight | 19.5 kg (43.0 lbs) instrument; 31.9 kg (70.3 lbs) incl. standard transport case; 37 kg (82 lbs) incl. large transport case |
Display | 7" LCD, Capacitive touch screen |
Available Languages | English, French, German, Spanish, Swedish |
Measurement | |
Current Measurement | |
Display Range | 0.0 to 2999.0 A |
Basic Inaccuracy | ±(0.5% of reading +0.1 A) |
Resolution | 0.1 A |
Internal Current Measurement | |
Range | 0 to 220 A |
Input for Clamp-on Probe | |
Range | 0 to 1000 mV DC |
mV/A-Ratio | 0.30 mV/A to 100.00 mV/A |
Input Impedance | >1 MΩ |
Voltage Measurement | |
Voltage | 0 to 500 V DC |
Inaccuracy | ±(0.5% of reading +0.1 V DC) |
Resolution | 0.1 V |
Sample Rate | 10 Hz, Values are saved when change is >10mV |
Time Measurement | |
Inaccuracy | ±0.1% of reading ±1 digit |
Load | |
Battery Voltage | 7.5 V to 300 V1)/500 V2) |
Power | 15 kW (max) |
Load Patterns | Constant current, constant power, constant resistance, current or power profile |
Constant I | |
Range | 0 to 220.0 A |
Inaccuracy | ±(0.5% +0.2 A) |
Resolution | 0.1 A |
Ripple Max | 0.5 A peak |
Constant R | |
Range | 300 mΩ to 3 kΩ |
Inaccuracy | ±1% typical |
Resolution | 100 mΩ |
Constant P | |
Range | 0 to 15 kW |
Inaccuracy | ±1% typical |
Resolution | 10 W |
Inputs | |
+ | 7.5 to 300 V.1) 7.5 to 500 V.2) |
– | 0 V |
I EXT ≤ 1 V | 1 V DC, 300 V DC to ground |
Voltage Sense | Impedance to the current terminals is >1 MΩ |
Outputs | |
Alarm | Relay contact 28 V DC, 8 A, 240 V AC, 8 A |
TXL Stop | Relay contact 250VDC, 0.28A, 28VDC, 8A, 250VAC, 8A |
9 V DC | 9 V DC, ±7% max 100 mA |
Communication Ports | |
BVM1 BVM2 | USB connection for BVM units |
USB | Connection for USB memory |
Service Port | You can find the full details in the Megger Torkel 950 Manual |